Tripp Lite SU10KRT3UHV Power Supply User Manual


 
Maintains continuous operation through blackouts, voltage fluctuations and surges with zero transfer time
Removes harmonic distortion, electrical impulses, frequency variations and other hard to solve power problems
10,000VA/8,000W power capacity with hardwire input/output connections
Accepts input voltages between 156 and 276, regulating output within 2% of selectable 200/208/220/230/240V AC output
Standard included 3U battery pack provides 10 minutes runtime at half load (5,000VA) and 4 minutes at full load (10,000VA)
Expandable runtime with multiple external battery packs, sold separately
Innovative design makes unit adaptable for rackmount, tower, or stacking applications
Power module and battery pack require only 3 rack spaces each (6U total rack space usage)
DB9 serial port for network interface; SNMP compatible
Slot for optional SNMP/Web card (part# SNMPWEBCARD)
PowerAlert unattended shutdown software and 6 ft. network cable included
Fault tolerant auto-bypass maintians continuous utility output to connected equipment, even in cases where the UPS is overloaded or
suffers an internal failure that requires service
Detachable hardwired PDU with manual bypass switch enables hot-swap UPS replacement without powering off connected loads
Diagnostic LEDs and LCD provide complete overview of operating conditions, UPS status and more
Mounting hardware included
Includes RJ11 EPO (emergency power off) port and interconnection cable
2 year manufacturers product warranty
$250,000 Ultimate Lifetime connected equipment insurance
Specifications
SYSTEM OVERVIEW
Voltage compatibility 208V AC (200/208/220/230/240V)
Frequency
compatibility
50/60Hz
OUTPUT
Output VA 10000
Output watts 8000
Output nominal
voltage
208V AC (200/220/230/240V)
Output voltage
regulation
Maintains pure sine wave output at all times, regulated within 2% of selected nominal output voltage, less than 5% total
harmonic distortion
Output frequency
regulation
Regulates line frequency to 50/60Hz +/- 0.05Hz
Outlet quantity / type Hardwire via detachable distribution module
INPUT
Maximum input amps 46.7A (200V), 44.9A (208V), 42.4A (220V), 40.6A (230V), 38.9A (240V) max.
Input connection type Hardwire via detachable distribution module
BATTERY
Full load runtime Included batteries — 4 min (10,000VA)
Half load runtime Included batteries — 10 min (5,000VA)
Expandable battery
runtime
Supports extended runtime with optional external battery packs
DC system voltage 240V DC
Typical battery
lifespan
3-6 years, depending on usage
Battery recharge rate Less than 8 hours to 90% (included battery set only)
VOLTAGE REGULATION
Voltage regulation
description
On-line, double-conversion process allows this UPS to maintain output voltage within +/-2% of selected nominal voltage
at all times
Overvoltage
correction
Maintains continuous operation without using battery power during overvoltages to 276V AC, reducing output within 2%
of selected nominal