Tripp Lite SU2200XLA Power Supply User Manual


 
True on-line, double conversion UPS provides a constant, pure sine wave AC output
Maintains continuous operation through blackouts, brownouts, voltage fluctuations and surges with zero transfer time
Zero transfer time, on-line, double-conversion and economy-mode operation supported
Removes harmonic distortion, electrical impulses, frequency variations and other hard-to-solve power problems
Accepts input voltages between 80V and 138V (65V to 138V at loads under 70%), regulating output to 120V AC +/-2%
2200VA/1600W output capacity with 7 total outlets (6 NEMA5-15/20R and 1 L5-20R)
Two built-in individually switchable load banks, each with three outets, can be controlled via software interface to selectively reboot remote
equipment or automatically shed less critical loads to extend battery runtime for the most critical equipment
Standard internal battery set provides 14 min. runtime at half load and 4.5 min. at full load
Runtime is expandable with BP48V24-2U (limit 1) or BP48V60RT3U (multi-pack compatible) external battery packs
Attractive all-black upright tower format
Simultaneous communications via HID-compliant USB port, serial port, and SNMP/web card slot
HID-compliant USB interface enables integration with built-in power management and auto shutdown features of Windows and Mac OS X
DB9 serial network interface supports RS-232 and contact closure messaging
Slot for optional SNMP/web card (part #: SNMPWEBCARD)
Included PowerAlert UPS Power Management Software and cabling provides monitoring of in-depth site power conditions, full UPS status
and fault warnings, output load level and load bank power control
Compatible with Tripp Lite's WatchDog Service Monitoring and Control Software (part# WATCHDOGSW)
Fault-tolerant auto-bypass maintains continuous utility output to connected equipment, even in cases where the UPS is overloaded or
suffers an internal failure that requires service
Diagnostic LEDs
$250,000 Ultimate Lifetime Insurance coverage for conbnected equipment(USA & Canada only)
2-year product warranty
Specifications
SYSTEM OVERVIEW
Voltage
compatibility
120V AC (110/120V)
Frequency
compatibility
50/60 Hz compatible (auto-sensing)
OUTPUT
Output VA 2200
Output watts 1600
Output nominal
voltage
120V AC (110/120V)
Output voltage
regulation
Maintains full-time sine wave output within 2% of selected nominal, less than 3% total harmonic distortion (linear load) /
5% total harmonic distortion (computer load) (Less than 5% THD on-line and on-battery)
Output frequency
regulation
Regulates line frequency to 50/60Hz +/- 0.05Hz
Outlet quantity /
type
6 x NEMA 5-15/20R, 1 x NEMA L5-20R
Customized load
management
receptacles
2 controllable load banks, each with 3 outlets, support load shedding and remote reboot on demand of locked network
devices
Overload protection 30A input breaker
INPUT
Maximum input
amps
16A (120V) / 17.6 (110V)
Input connection
type
NEMA 5-20P (user-installable NEMA 5-15P also included)
Input cord length 10ft / 3m
Recommended
Electrical Service
120V 20A dedicated circuit
BATTERY