Tyco 917 Computer Drive User Manual


 
Kunkle Safety and Relief Products
Tyco reserves the right to change product design and specifications KUKMC-0392
without notice. Copyright © 2002 by Tyco International Ltd. 21
Models 910, 911, 912, 913, 916, 917, 918, 919, 920, 921 and 927
Models 910, 911, 912, 913, 916, 917, 918, 919
Non-code Liquid - 25% Accumulation, [Metric, m
3
/h]
Flow Coefficient = 0.710
Set Pressure ———–—————— Orifice Area, cm
2
——––—––—————
[barg] D E F G H J
[0.783] [1.392] [2.174] [3.568] [5.574] [9.129]
Note
1. Pressure Limitations
Models 910, 916: 0.2 to 62 barg
Models 911, 917: 0.2 to 62 barg
Models 912, 918: 0.2 to 20.7 barg
Models 913, 919: 0.2 to 62 barg
0.2 1 3 4 6 10 17
0.5 2 4 6 10 16 26
1.0 3 6 9 14 23 37
2.0 4 8 12 20 32 52
3.0 5 10 15 253964
4.0 6 11 18 294574
5.0 7 13 20 325083
6.0 8 14 22 355590
7.0 8 15 23 386098
8.0 9 16 25 4164104
9.0 9 17 26 4368111
10.0 10 18 28 46 71 117
12.0 11 19 30 50 78 128
14.0 12 21 33 54 84 138
16.0 13 23 35 58 90 148
18.0 13 24 37 61 96 157
20.0 14 25 39 65 101 165
22.0 15 26 41 68 106 173
24.0 16 28 43 71 110 181
26.0 16 29 45 74 115 188
28.0 17 30 47 76 119 195
30.0 17 31 48 79 123 202
32.0 18 32 50 82 128 209
34.0 18 33 51 84 131 215
36.0 19 34 53 87
38.0 20 35 54 89
40.0 20 36 56 91
42.0 21 36
44.0 21 37
46.0 21 38
48.0 22 39
50.0 22 40
52.0 23 41
54.0 23 41
56.0 24 42
58.0 24 43
60.0 25 44
62.0 25 44