4. Installation
This Section provides further details regarding the connections that are
made in the process of installing the IPS unit.
4.1. Power Supply Connection
Use the supplied power cord to connect the IPS unit to an appropriate
power supply. Connect the Power Supply cord to the IPS Power Inlet, and
then snap the cable keeper into place. The IPS’s Master Power Switch must
be "On" in order for the unit to operate.
CAUTIONS:
Before attempting to install this unit, please review the
warnings and cautions listed at the front of the user's guide.
This device should only be operated with the type of power
source indicated on the instrument nameplate. If you are
not sure of the type of power service available, please contact
your local power company.
Reliable earthing (grounding) of this unit must be
maintained. Particular attention should be given to supply
connections when connecting to power strips, rather than
directly to the branch circuit.
Check nameplate ratings to ensure that there is no
overloading of supply circuits that could have an effect on
overcurrent protection and supply wiring.
4.2. Connection to Switched Outlets
Connect the power cord from the Switched Device to a Switched AC Outlet
on the IPS unit. When power is applied to the IPS unit for the first time, all
four AC Outlets will be switched "ON".
The IPS-400 can switch up to a total of 15 Amps, and the IPS-400-CE can
switch up to a total of 10 Amps.