Western Telematic MPC-20VS30-1 Network Card User Manual


 
3-2
Getting Started
Model No.
Input
Feeds
Input
Voltage
Max. Load
per Outlet
Max. Load
per Input
Max. Load
per Unit
MPC-8H-1 2 ea, 20 Amp 100 to 120 VAC 16 Amps 16 Amps * 32 Amps *
MPC-8H-2
2 ea, 16 Amp 100 to 240 VAC 10 Amps 16 Amps * 32 Amps *
MPC-16H-1
2 ea, 20 Amp 100 to 120 VAC 16 Amps 16 Amps * 32 Amps *
MPC-16H-2
2 ea, 16 Amp 100 to 240 VAC 10 Amps 16 Amps * 32 Amps *
MPC-18H-1
1 ea, 20 Amp 100 to 120 VAC 16 Amps 16 Amps * 16 Amps *
MPC-18H-2
1 ea, 16 Amp 100 to 240 VAC 10 Amps 16 Amps * 16 Amps *
MPC-20V-1
2 ea, 20 Amp 100 to 120 VAC 16 Amps 16 Amps * 32 Amps *
MPC-20V-2
2 ea, 16 Amp 100 to 240 VAC 15 Amps 16 Amps * 32 Amps *
MPC-20VS20-1
1 ea, 20 Amp 100 to 120 VAC 16 Amps 16 Amps * 16 Amps *
MPC-20VS20-2
1 ea, 16 Amp 100 to 240 VAC 15 Amps 16 Amps * 16 Amps *
MPC-20VD20-1
2 ea, 20 Amp 100 to 120 VAC 16 Amps 16 Amps * 32 Amps *
MPC-20VD20-2
2 ea, 20 Amp 100 to 240 VAC 15 Amps 16 Amps * 32 Amps *
MPC-20VS30-1
1 ea, 30 Amp 100 to 120 VAC 20 Amps 24 Amps * 24 Amps *
MPC-20VS30-2
1 ea, 30 Amp 100 to 240 VAC 15 Amps 24 Amps * 24 Amps *
MPC-20VD30-1
2 ea, 30 Amp 100 to 120 VAC 20 Amps 24 Amps * 48 Amps *
MPC-20VD30-2
2 ea, 30 Amp 100 to 240 VAC 15 Amps 24 Amps * 48 Amps *
MPC-20VS16-3
1 ea, 16 Amp 100 to 240 VAC 10 Amps 16 Amps 16 Amps
MPC-20VD16-3
2 ea, 16 Amp 100 to 240 VAC 10 Amps 16 Amps 32 Amps
MPC-20VS32-3
1 ea, 32 Amp 100 to 240 VAC 10 Amps 32 Amps 32 Amps
MPC-20VD32-3
2 ea, 32 Amp 100 to 240 VAC 10 Amps 32 Amps 64 Amps
* In accordance with UL requirements for branch circuits, this value has been
de-rated to 80%.
Notes:
MPC-H Series model numbers that end with the “-1” suffix include 20 Amp
Circuit Breaker(s).
MPC-H Series model numbers that end with the “-2” suffix include 16 Amp
Circuit Breaker(s).
MPC-V Series model numbers that end with “-3” include 16 Amp Circuit
Breaker(s).
MPC-V Series model numbers that end with “-1” or “-2” include 20 Amp
Circuit Breaker(s). The only exception is the MPC-20V-2, which includes 16
Amp Circuit Breakers.
To determine the exact model number for your MPC unit, either refer to the
nameplate on the back of the unit, or access command mode as described
in Section 3.2 and invoke the Product Status command; in the Text Interface,
type /J * and press [Enter]; in the Web Browser Interface, click on the
"Product Status" Link on the left hand side of the screen.