Web/SNMP Management SmartSlot Card User’s Guide 38
Device Manager Menus
UPS Status Options
continued
Output voltage,
continued
Silcon DP300E.
Five status fields report the output values for a Silcon
DP300E series UPS.
Note:
In the Control Console, use the
Detailed UPS Information
option to access the
Peak Output Current
status.
Fault tolerance
(Symmetra
Power
Array
)
Two status fields report the Symmetra Power Array fault tolerance.
Note:
In the Control Console, you use the
Detailed UPS Information
option to access the fault tolerance status.
Continued on next page
Status Field Definition
Output Voltage
How much AC voltage the
UPS
is providing to its attached
equipment for each phase.
Output Current
How much current the output voltage is providing for each
phase.
Output Power
The load placed on each phase by the attached equipment, in
total kVA.
Output Power
Percentage
The load placed on each phase by the attached equipment,
expressed as a percentage of the of the kVA available from the
UPS
.
Peak Output
Current
The highest current output by each phase.
Status Field Definition
Redundancy
The number of power modules which can fail or be removed
without causing the Symmetra Power Array to generate a
Minimum Redundancy Lost event.
Present KVA
Capacity
The maximum load that the Symmetra Power Array can
support.