A SERVICE OF

logo

6 CB20-EU-EN-V1.2 5/13
ReceptacleWiringTest
1. PlugtheTransmitter/Receptacletesterintotheoutlet.
2. ThethreeLED’swillindicatecircuitcondition.Thediagramlistsalloftheconditionsthatthe
CB20candetect.TheLED’sinthisdiagramrepresenttheviewfromtheGFCIbuttonsideof
thetransmitter.WhenviewingtheothersideofthetransmittertheLED’swillbeamirror
imageofthoseshownhere.
3. Thetesterwillnotindicatethequalityofthe groundconnection,2hotwiresinacircuit,a
combinationofdefects,orreversalofgroundandneutralconductors.
ReceptacleGFCITest
1. Beforeusingthetester,presstheTESTbuttonontheinstalledGFCIreceptacle,theGFCI
shouldtrip.Ifitdoesnottrip,donotusethecircuitandcallaqualifiedelectrician.Ifitdoes
trip,presstheRESETbuttononthereceptacle.
2. PlugtheTransmitter/Receptacletester
intotheoutlet.Verifythatthewiringiscorrectas
describedabove.
3. Pressandholdthetestbuttononthetesterforatleast8seconds,theindicatorlightson
thetesterwillshutoffwhentheGFCItrips.
4. Ifthecircuitdoesnottrip,eitherthewiring
isincorrect,orthewiringiscorrectan dtheGFCI
isdefective.
CORRECT WIRING
GFCI TESTING IN PROGRESS
HOT ON NEUTRAL WITH HOT OPEN
HOT AND GROUND REVERSED
HOT AND NEUTRAL REVERSED
OPEN HOT
OPEN NEUTRAL
OPEN GROUND
OFF
ON