FS-8700-97_Lutron_Machine Manual Page 9 of 11
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldserver.com
4.3. Client Side Node Descriptors
Section Title
Nodes
Column Title Function Legal Values
Node_Name Provide name for node Up to 32 alphanumeric characters
Node_ID
The eLumen processor address.
Only decimal values are allowed:
e.g. 11 hex must be entered as
17.
0-255
Protocol Specify protocol used eLumen
Connection
Specify which port the device is
connected to the FieldServer
P1-P8, R1-R2
1
Node_type
Specifies the eLumen command
and data format
Hex, decimal
Example
// Client Side Nodes
Nodes
Node_Name, Node_ID, Protocol, Port, Node_Type
LUT_GRF6_0, 17, eLumen, P1, Hex
4.4. Client Side Map Descriptors
4.4.1. FieldServer Related Map Descriptor Parameters
Column Title Function Legal Values
Map_Descriptor_Name
Name of this Map
Descriptor
Up to 32 alphanumeric
characters
Data_Array_Name
Name of Data Array
where data is to be
stored in the
FieldServer
One of the Data Array
names from “Data Array”
section above
Data_Array_Offset
Starting location in Data
Array
0 to maximum specified in
“Data Array” section above
Function
Function of Client Map
Descriptor
ARCO, AWT, RDBC,
Passive_Client
4.4.2. Driver Related Map Descriptor Parameters
Column Title Function Legal Values
Node_Name Name of Node to fetch data from
One of the node names
specified in “Client Node
Descriptor” above
Grafik_Command
Specifies the command that will be
sent to the eLumen.
Area Machine:
run_script_AB
area_sts_offscene
sel_scene_in_area
run_script_multi