A SERVICE OF

logo

19
Powerware
®
3115 User’s Guide www.powerware.com
CHAPTER 5
SPECIFICATIONS
This section provides the following specifications for the
Powerware 3115 models:
Electrical input and output
Battery
Weights and dimensions
Environmental and safety
Table 3. Model List
120V Models 230V Models
UPS Models PW3 300
PW3 420
PW3 650
PW3 300i
PW3 420i
PW3 650i
Table 4. Electrical Input
120V Models 230V Models
Nominal Voltage 120V default; 110, 120, 127V selectable 230V default; 220, 230, 240V selectable
Power Factor 0.6
Voltage Range User-selectable:
88V - 142V
93V - 142V
98V - 142V
103V - 142V (default)
User-selectable:
166V - 260V
176V - 260V
186V - 260V
196V - 260V (default)
Nominal Frequency 50/60 Hz
Online Efficiency 96%
Noise Filtering Full-time EMI/RFI filtering
Overcurrent
Protection
10A, resettable circuit breaker PW3 300i: 3.15A fuse (12.6A fault current)
PW3 420i: 3.15A fuse (12.6A fault current)
PW3 650i: 6.3A fuse (25.2A fault current)
Connections 6-foot power cord with a 5-15 plug (90° angle) 10A, IEC-320, input connector with fuse