A SERVICE OF

logo

6
Configuration
(continued)
Voltage 9, 10 Switch Position
180 VAC Up, Up
170 VAC Up, Down
160 VAC Down, Up
150 VAC Down, Down (factory setting)
230V Operation (APSX3024SW)
270 V
260 V
Select High AC Input Voltage Point for
Switching to Battery - OPTIONAL*
Voltage Switch Position
270 VAC Up
260 VAC Down (factory setting)
11
9 10 11 12
270 V
260 V
Select High AC Input Voltage Point for
Switching to Battery - OPTIONAL*
Voltage Switch Position
270 VAC Up
260 VAC Down (factory setting)
11
9 10 11 12
Select Low VAC Input Voltage Point for Switching to Battery
- OPTIONAL*
109
9 10 11 12
9 10 11 12
9 10 11 12
9 10 11 12
Voltage 9, 10 Switch Position
180 VAC Up, Up
170 VAC Up, Down
180 VAC Down, Up
170 VAC Down, Down (factory setting)
230V Operation (APSX6048VR model with Switch #4 in “Down” position)
Select Low VAC Input Voltage Point for Switching to Battery
109
9 10 11 12
9 10 11 12
9 10 11 12
9 10 11 12
208V Operation (APSX6048VR model with Switch #4 in “Up” position)
Select High AC Input Voltage Point for
Switching to Battery - OPTIONAL*
Voltage Switch Position
245 VAC Up
235 VAC Down (factory setting)
11
245 V
235 V
9 10 11 12
Select Low VAC Input Voltage Point for Switching to Battery
- OPTIONAL*
109
Voltage 9, 10 Switch Position
175 VAC Up, Up
165 VAC Up, Down
175 VAC Down, Up
165 VAC Down, Down (factory setting)
9 10 11 12
9 10 11 12
9 10 11 12
9 10 11 12


Low AC Voltage Point, you will reduce the number of times your unit switches to battery due to voltage swings.