AB Soft MS6 SERIES Network Card User Manual


 
Opal Pro to Mod TCP
Page 11
Output
Words
(Polled)
AB Ethernet
IP
Name Description
Bit 0 – Ready to Run (drive is enable
and has 3 phase power)
Bit 1 –Running (start is regulating)
Bit 2 – Full On (starter is phased fully
on)
Bit 3 – Up to Speed (started is
phased fully on and the current is
below 105% of nameplate current as
set in 13.01)
Bit 4 – Reverse
Bit 5 – Jogging
Bit 6 – DC Injecting
Bit 7 – Faulted
Bit 8 – IOC Fault
Bit 9 – MOL Fault
Bit 10 – Phase Loss Fault
Bit 11 – Shear Pin Fault
Bit 12 – Shorted SCR Fault
Bit 13 – Heat Sink OT Fault
Bit 14 – Reserved
Word 1 Input Word 0 Status
Bit 15 – Watch Dog Bit
Word 2 Input Word 1 Current
Feedback
833 = 500% of motor name plate
current as set in 13.01
Word 3 Input Word 2 Phase Angle
Actual
Amount of time phased on in
microseconds
Parameter AB Ethernet
IP
Name Description
1.01 Input Word 3 Current Current feedback in Amps
1.02 Input Word 4 L1 to L2
Voltage
Line 1 to Line 2 Voltage in Volts
1.03 Input Word 5 L1 to L3
Voltage
Line 1 to Line 3 Voltage in Volts
1.04 Input Word 6 L2 to L3
Voltage
Line 2 to Line 3 Voltage in Volts
Digital input status
Bit 0 – Start
Bit 1 – Stop
Bit 2 – Jog
Bit 3 – Reverse
1.05 Input Word 7 DI Status
Bit 4 – Reset
1.06 Input Word 8 Analog Input Analog input value in Volts X 100