AB Soft MS6 SERIES Network Card User Manual


 
Opal Pro to Mod TCP
Page 12
Relay Status Status of the Relay Outputs
Bit 0 – Running
Bit 1 – By-Pass
Bit 2 – Shorted SCR
Bit 3 – Reverse
1.07 Input Word 9
Bit 4 – Faulted
1.08 Input Word
10
Analog Output
Analog Output value in Volts X 100
2.01 Input Word
11
Stack Size Opal Pro Stack Size in Amps
2.02 Input Word
12
Comm
Module Type
0 – None
2 – Ethernet
2.03 Input Word
13
Firmware
Version
Opal Pro Firmware Version x 100
10.01 Input Word
14
Start/Stop
Control
4 = 2 Wire
5 = 3 Wire
6 = Comm Module
10.02 Input Word
15
Ramp Time Time is seconds
10.03 Input Word
16
Step Current In % of nameplate current
10.04 Input Word
17
Current
Reference
7 = Internal
8 = Analog Input
9 = Comm Module
10.05 Input Word
18
Phase Angle 10 = Internal
11 = Analog Input
12 = Comm Module
10.06 Input Word
19
Jog Accel
Current Limit
In % of nameplate current
10.07 Input Word
20
Jog Current
Limit
In % of nameplate current
10.08 Input Word
21
Jog Ramp Time is seconds x 10
11.01 Input Word
22
Stop Mode 13 = Coast
14 = Soft Stop
15 = DC Injection
11.02 Input Word
23
Soft Stop
Step
In % of incoming line voltage
11.03 Input Word
24
Soft Stop
Ramp
Time in seconds
11.04 Input Word
25
DCI Current In % of nameplate current
11.05 Input Word
26
DCI Time Time in seconds