ADC X21 Switch User Manual


 
ADCP-50-304 • Issue 19 • June 1999 • Section 5: Site Preparation
Page 5-1
© 1999, ADC Telecommunications, Inc.
SECTION 5: SITE PREPARATION
1 GENERAL. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5-1
2 SPACE REQUIREMENTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5-1
3 ENVIRONMENTAL CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5-1
4 POWER REQUIREMENTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5-1
_________________________________________________________________________________________________________
1 GENERAL
This section contains the information necessary to prepare a facility for installing the
PatchSwitch hardware.
2 SPACE REQUIREMENTS
All PatchSwitch chassis are normally installed into existing standard 19-inch racks (or in 23-
inch racks with appropriate adapters). Each chassis occupies a rack space of 7 inches in height
and 12 inches in depth.
Prior to installation, select the rack positions in the system where the chassis and other units of
PatchSwitch equipment are to be located.
3 ENVIRONMENTAL CONSIDERATIONS
The allowable ambient temperature range for shipping or storage is –40
°
F to +158
°
F (–40
°
C
to + 70
°
C). For operation, the allowable ambient temperature range is from +32
°
F to +122
°
F
(0
°
C to +50
°
C). The relative humidity may vary from 10% to 80% in the range of +32
°
F to
+122
°
F (0
°
C to +50
°
C) provided there is no condensation.
4 POWER REQUIREMENTS
Each PS chassis uses a power supply that requires a source of 110 Vac, 60Hz (or 220 Vac, 50
Hz) single phase commercial power. The PSW-000001 or PSW-000003 power supplies are
stand-alone ac to dc converters with six-foot line power cords and six-foot chassis power cords.
Convenience outlets must be within 12 feet of the chassis rear power connector.
Content Page