Advantech ADAM 4000 Network Card User Manual


 
Chapter 5
5-7
ADAM 4000 Series User’s Manual
4011, 4011D, 4012, 4013, 4015, 4015T, 4016,
4017, 4017+, 4018, 4018+, 4018M, 4019+
Input Range Code (Hex) Input Range for 4013
20
Platinum, -100 ~ 100 , a=0.00385
21
Platinum, 0 ~ 100 , a=0.00385
22
Platinum, 0 ~ 200 , a=0.00385
23
Platinum, 0 ~ 600 , a=0.00385
24
Platinum, -100 ~ 100 , a=0.003916
25
Platinum, 0 ~ 100 , a=0.003916
26
Platinum, 0 ~ 200 , a=0.003916
27
Platinum, 0 ~ 600 , a=0.003916
28
Nickel, -80 ~ 100
29
Nickel, 0 ~ 100
ADAM-4015/4015T command codes against Input ranges table
Command Code (Hex) Input Type Input Range
20 Platinum 100 (IEC)
-50 ~ 150
21 Platinum 100 (IEC)
0 ~ 100
22 Platinum 100 (IEC)
0 ~ 200
23 Platinum 100 (IEC)
0 ~ 400
24 Platinum 100 (IEC)
-200 ~ 200
25 Platinum 100 (JIS)
-50 ~ 150
26 Platinum 100 (JIS)
0 ~ 100
27 Platinum 100 (JIS)
0 ~ 200
28 Platinum 100 (JIS)
0 ~ 400
29 Platinum 100 (JIS)
-200 ~ 200
2A Platinum 1000
-40 ~ 160
2B BALCO 500
-30 ~ 120
2C Ni 604
-80 ~ 100
2D Ni 604
0 ~ 100
IEC RTD 100O, α = 0.00385
JIS RTD 100O, α = 0.00391