40
5) Select SETUP, 6) E.g. if the number of
e.g. REDUNDAN and redundant modules is 0, …
press ↵ / Return
The redundancy setup applies after the Setup menu is exited,
i.e. the UPS displays "Overload" if the power is more than
8 kVA / 5.6 kW.
7) Switch on the PROTECT 1.M in battery mode:
Having ensured that the batteries are connected correctly,
switch the battery fuse-switch disconnector to "ON". Then
press the system switch (located behind the LC display)
from "OFF" to "ON". The displayed menu is similar to that
of mains current mode. Now switch on the UPS. The UPS
switches off if you do not start any action within
15 seconds; the LC display is switched off after about
10 minutes: "NO MODULE DETECTED"
Observe the safety precaution!
For personal safety reasons, do not switch on the
UPS when the mains is disconnected!
SETUP REDUNDANCE
TOTAL NUM: 3
ÆREDUN NUM: 1
MAX POWER CURRENT
SETTING: 8kVA/5.6kW
WARNING:
CURRENT SETTING IS
NO REDUNDANCY, OK?
YES Æ NO