Parallel system with PROTECT 1.150
Number of UPS units
Available power
1 2 3
0 15 kVA 30 kVA 45 kVA
1 --- 15 kVA 30 kVA
Active
redundancy
degree
2 --- --- 15 kVA
Parallel system with PROTECT 1.200
Number of UPS units
Available power
1 2 3
0 20 kVA 40 kVA 60 kVA
1 --- 20 kVA 40 kVA
Active
redundancy
degree
2 --- --- 20 kVA