AEG Protect 1.1 Power Supply User Manual


 
30
Mechanically secure the cables with the strain relief
clamps of the cable clamping unit.
Mount the connection cover of the cable clamping unit.
5.3.1 Connection Cross-Sections and Fuse Protection
The required dimensions can be found in the following table:
PROTECT
1.100
PROTECT
1.150*
PROTECT
1.200*
Max. current consumption
(bypass)
46A 68A 91A
Incoming mains
cable (UPS input)
min.
max.
10 mm²
16 mm²
16 mm²
35 mm²
25 mm²
35 mm²
Load connection
(UPS output)
min.
max.
10 mm²
16 mm²
16 mm²
35 mm²
25 mm²
35 mm²
Battery connection Via enclosed
battery
connection
cable protect-
ted against
polarity
reversal
Min. 16 mm², Max. 35
mm² per terminal
Battery connection cable
is included with the
battery unit
Observe earth-fault- and
short-circuit-proof routing!
Mains fuse (UPS input) 50A gl 80A gl 100A gl
When using line safety switches, observe
trigger characteristic: “D”
Line safety switch “B” characteristicLoad fuse (recommended
max.)
16A 20A 25A
* To ensure a reliable strain relief, individual wires must be
laid especially for connecting the 15 and 20 kVA UPS
systems.
Recommended connection cable acc. to VDE 0298-4:
Specially for 15 and 20 kVA: Special rubber-insulated wire
NSGAÖU or NSGAFÖU
or NYY or
Radox 4GKW-AX
e.g. Huber & Suhner