American Power Conversion 208 VAC Power Supply User Manual


 
10 Smart-UPS 2200/3000 VA XL 120/208/230 VAC Tower/Rack-Mount 5U User Manual
Indicator
LED
Indicator Title Description
Diagnostic
Utility Voltage
The UPS has a diagnostic feature that indicates the utility voltage.
The UPS starts a self-test as part of this procedure. The self-test does not affect
the voltage display.
Press and hold the button to view the utility voltage bar graph indicator.
After a few seconds, this five-LED Battery Charge indicator on the right of
the display panel will show the utility input voltage.
Refer to the figure on the left for the voltage reading.
Values are not listed on the UPS.
The indicator on the UPS shows the voltage is between the displayed value on
the list and the next higher value, (see Troubleshooting).
Feature
Button
Feature Title Function
Power On Press this button to turn on the UPS. Continue reading for additional
capabilities.
Self-Test Automatic: The UPS performs a self-test automatically when tuned on, and
every two weeks thereafter (by default). During the self-test, the UPS
briefly operates the connected equipment on battery.
Manual: Press and hold the
button for a few seconds to initiate the
self-test.
Cold Start When there is no utility power and the UPS is off, the cold start feature will
switch the UPS and connected equipment onto battery power,
(see Troubleshooting).
Power Off Press this button to turn off the UPS.
230 V
208 V
Battery
Charge
120 V
Battery
Charge