American Power Conversion 220 VAC Power Supply User Manual


 
11
USER CONFIGURABLE ITEMS
NOTE: SETTINGS ARE MADE THROUGH SUPPLIED POWERCHUTE SOFTWARE, SMART SLOT
ACCESSORY CARDS, OR TERMINAL MODE.
FUNCTION
F
ACTORY
DEFAULT
USER SELECTABLE
CHOICES
D
ESCRIPTION
Automatic Self-Test Every 14 days
(336 hours)
Every 7 days(168 hours),
14 days (336 hours)
On Startup Only,
No Self-Test
Set the interval at which the
UPS will execute a self-test.
UPS ID UPS_IDEN Up to eight characters to
define the UPS
Uniquely identify the UPS, (i.e.
server name or location) for
network management purposes.
Date of Last Battery
Replacement
Manufacture Date Date of
Battery Replacement
mm/dd/yy
Reset this date when you replace
the battery module.
Minimum Capacity
Before Return from
Shutdown
0 percent 0, 15, 25, 35, 50, 60, 75,
90 percent
Following a low-battery
shutdown, the batteries will be
charged to the specified
percentage before powering
connected equipment.
Alarm Delay After
Line Failure
5 second delay 5 or 30 second delay
At Low Battery
Never
Mute ongoing alarms or disable
all alarms permanently.
Shutdown Delay 20 seconds 0, 20, 60, 120, 240, 480,
720, 960 seconds
Set the interval between the time
when the UPS receives a
shutdown command and the
actual shutdown.
Duration of
Low Battery Warning.
2 minutes
PowerChute
software provides
automatic,
unattended
shutdown when
approximately 2
minutes of battery
operated runtime
remains.
2, 5, 7, 10, 12, 15, 18,
20 minutes
The low battery warning beeps
are continuous when two
minutes of run time remain.
Change the warning interval
default to a higher setting if the
operating system requires a
longer interval for shutdown.
Synchronized Turn-on
Delay
0 seconds 0, 20, 60, 120, 240, 480,
720, 960 seconds
The UPS will wait the specified
time after the return of utility
power before turn-on (to avoid
branch circuit overload).