American Power Conversion 3000 VA Power Supply User Manual


 
10 Smart-UPS 2200/3000 VA 100/120/230 VAC Tower User Manual
Configuration
Low Battery
Warning
2 minutes
PowerChute
software
interface
provides
automatic,
unattended
shutdown when
approximately
two minutes of
battery operated
run time
remains.
Brightly
illuminated:
low battery warning
level of about 2 minutes
Dimly illuminated:
low battery
warning level of about
5 minutes
No illumination:
low battery warning
level is about 8 minutes
The low-battery warning beeps are continuous
when two minutes of run time remain.
To change the default interval setting, use a
pointed object such as a pen to press the
VOLTAGE SENSITIVIY switch (rear
panel), while
pressing the button, (front display).
Change the low battery warning interval setting
to the time that the operating system or system
software requires to safely shut down.
Synchronized
Turn-on Delay
0 seconds 0 s
•60 s
•120 s
•180 s
240 s
300 s
360 s
420 s
Specify the time the UPS will wait after the
return of utility power before start up, (to avoid
branch circuit overload).
High Transfer Point 100 V models:
108 VAC
120 V models:
127 VAC
230 V models:
253 VAC
•108 VAC
•110 VAC
•127 VAC
•130 VAC
•253 VAC
•257 VAC
•112 VAC
•114 VAC
133 VAC
136 VAC
261 VAC
265 VAC
To avoid unnecessary use of the battery where
utility voltage is chronically high, set the high
transfer point higher if the connected
equipment can tolerate this condition.
Low Transfer Point 100 V models:
92 VAC
120 V models:
106 VAC
230 V models:
208 VAC
•86 VAC
•88 VAC
•97 VAC
•100 VAC
•196 VAC
•200 VAC
•90 VAC
•92 VAC
103 VAC
106 VAC
204 VAC
208 VAC
To avoid unnecessary use of the battery where
utility voltage is chronically low, set the low
transfer point lower if the connected equipment
can tolerate this condition.
Output Voltage
230 V models 230 VAC
220 VAC 240 VAC
230 V models only: Sets the output voltage of
the UPS.
Function
Factory
Default
User Selectable
Choices Description