American Power Conversion 400 Power Supply User Manual


 
20
5.4.2 Option Switch 2
Option Switch 2 functions differently for different versions of the UPS.
100 Vac version
No function; not used.
120 Vac version
The UPS’s factory-set input voltage limits for on-line and SmartBoost
operation are centered on the nominal input voltage of 120 Vac (see also
Sec. 9.1). When Option Switch 2 is in the on (down) position, the upper and
lower transfer voltages are lowered by 4% and centered on a nominal input
of 115 Vac. This is useful where nominal input voltage is 110 to 115 Vac.
220/230/240 Vac version
The UPS’s factory-set on-battery output voltage and input voltage limits for
on-line and SmartBoost operation are designed for use in regions where the
nominal line voltage is 220 to 230 Vac. When Option Switch 2 is set to the
on (down) position, the upper and lower transfer voltages are raised by 4%
and centered on a nominal input of 240 Vac. In addition, the on-battery
output voltage is increased to 240 Vac.
5.4.3 Option Switch 3
When Option Switch 3 is set to the on (down) position, the UPS’s audible
alarm is disabled for the first 30 seconds of on-battery operation. This
function is useful where brief power interruptions are frequent and cause
the alarm to become annoying.
5.4.4 Option Switch 4
When Option Switch 4 is set to the on (down) position, the UPS’s Auto-on
mode is disabled, and the UPS must be turned on and off with the rear-
panel UPS Enable switch. When Option Switch 4 is set to the off (up)
position, the UPS and the devices plugged into the accessory outlets are
turned on when the device plugged into the master outlet is turned on.
Refer to Section 4.4 for more information about Auto-on operation.
The factory default setting for Switch 4 is down (Auto-on disabled).