American Power Conversion 5000I Power Supply User Manual


 
990-7032A, Revision 3 7/01 12
Specifications
Acceptable input voltage 0 - 325 VAC
Output voltage 196 - 253 VAC
Input protection Resettable circuit breaker
Frequency limits (on-line operation) 47 - 63 Hz
Transfer time 2 ms typical, 4 ms maximum
Maximum load, total 5000 VA/3750 W
On-battery output voltage 220, 225, 230, or 240 VAC
On-battery frequency 50 or 60 Hz, 0.1 Hz;
unless synchronized to utility during brownout
On-battery waveshape Low-distortion sine wave
Overload protection (on-battery) Overcurrent and short-circuit protected, latching shutdown on overload
Noise filter Normal and common mode EMI/RFI suppression,
100 kHz to 10 MHz
Battery type Spill proof, maintenance free, sealed lead-acid
Typical battery life 3 to 6 years, depending on number of discharge cycles
and ambient temperature
Typical recharge time 2 to 5 hours from total discharge
Operating temperature 0 to 40ΓC (+32 to +104ΓF)
Storage temperature -15 to +45ΓC (+5 to +113ΓF)
Operating and storage relative humidity 0 to 95%, non-condensing
Operating elevation 0 to +3,000 m (0 to +10,000 ft.)
Storage elevation 0 to +15,000 m (0 to +50,000 ft.)
Electromagnetic Compatibility (EMC) EN50091-2
Electromagnetic Interference (EMI) EN55022 Class A
Electromagnetic Immunity IEC 801-2, 801-3, 801-4, 801-5, 1000-2-2
EN60555-1, -2, -3, EN61000-4-1, EN61000-4-11
Audible noise in dBA at 1 m (3 ft.) z55
Safety approvals GS licensed by VDE to EN50091-1-1 and 60950
Rack Mount Units
RM Unit
Size (W x H x D)
43.2 x 19.6 x 62.2 cm
(17.0 x 8.7 x 24.5 in.)
Weight - net (shipping) 205 (235) lb.
93 (106.6) kg
Tower Units
Tower Unit
Size (W x H x D) 19.6 x 43.2 x 62.2 cm
(8.7 x 17.5 x 26.0 in.)
Weight - net (shipping) 200 (240) lb.
93 (106.6) kg