Basic and Metered Rack Power Distribution Unit 7
Operation
Display interface
(AP7862J only)
Link - Rx/Tx
10
/
100
Status
Serial Port
Reset
Press to
select line.
Press and hold
to invert display.
- Warning
- OK
- Overload
L3L2L1
Amps
Amps
Phase Indicator LEDs:
Indicates the phase corresponding to the current listed in the digital
display.
• Indicates normal (green), warning (yellow) or alarm (red)
condition.
Control button:
• Press to change the phase of the current displayed on the digital
display.
• Press and hold for five seconds to view the orientation; hold for an
additional five seconds to change the orientation.
• Press to silence an alarm.
Ethernet port: Connects the PDU to your network, using a CAT5
network cable.
Status LED: Indicates the status of the ethernet LAN connection and
the state of the
Metered PDU.
Link LED: Indicates whether there is activity on the network.
Serial port: Access internal menus by connecting this port (RJ-11
modular port) to a serial port on your computer, using the supplied
serial cable (part number
940-0144).
Display of the current used by the PDU and attached devices:
• Shows the aggregate current for the phase corresponding to the
Phase Indicator
LED that is illuminated.
• Cycles through all three phases in 3-second intervals.