American Power Conversion AP7862J Power Supply User Manual


 
Basic and Metered Rack Power Distribution Unit 1
Product Description and Inventory
Description
This manual provides information on installing and operating the
following three-phase Rack Power Distribution Units (
PDUs):
Metered PDU
AP7862J:
NEMA L21-20 plug 42 NEMA 5-15 outlets
Basic PDU
AP7562J:
NEMA L21-20 plug 42 NEMA 5-15 outlets
Metered PDU —Metered PDUs distribute power to devices in the
rack. These
PDUs have a sensor that measures the current being
used by the
PDU and it’s attached devices. The sensor can be
monitored through Web, Control Console,
SNMP, or InfraStruXure
Manager interfaces.
Basic PDU—Basic PDUs distribute power to devices in the rack.
Display Interface—The display interface on Metered PDUs
shows the aggregate current being used by the
PDU and its
attached devices. An alarm occurs if the aggregate current is above
the high threshold value or below the low threshold values that
you configure.
L21-20 plug—Both PDUs have an L21-20 plug, which connects to
a variety of
APC equipment, including InfraStruXure PDU power
cables and Rack Automatic Transfer Switches.