American Power Conversion Back-UPS CS 500 Power Supply User Manual


 
Item Type Specification
Input Voltage 220 Vrms Nominal
Frequency 45-55 Hz
Brownout Transfer 165 Vrms, typical
Over-voltage Transfer 266 Vrms, typical
Output UPS Capacity (total) 500 VA / 300 W
Voltage - On Battery 220 Vrms + 8%
(step-approximated sine wave)
Frequency - On Battery 120 Hz + 3 Hz
Transfer Time 8 ms typical, 10 ms maximum
Protection and Filter AC Surge Protection Full time, 160 joules
Overcurrent Protection Resettable circuit breaker
Battery (lead-acid) Type (maintenance free) 12V, 4.5 amp-hour
Average Life 2-5 years
Typical Recharge Time 16 hours
Physical Net Weight 7.2 lb. (3.3 kg.)
Size 13.3 (H) x 8.2 (W) x 21.3 (D) cm
Operating Temperature
0
o
C to 40
o
C
Storage Temperature
-15
o
C to 45
o
C
Operating Relative Humidity 5 to 95% non-condensing
Operating Elevation 0 to 10,000 ft (0 to 3,000 m)
Specifications
Warranty
Service
Contact Information
The standard warranty is 2 years from the date of purchase. APC will ship the replacement unit once
the defective unit is received by the repair department or cross-ship upon the provision of a valid
credit card number. The customer pays for shipping to APC, and APC pays ground freight
transportation costs back to the customer.
Please DO NOT RETURN the unit to the place of purchase under any circumstances.
1. Consult the Troubleshooting section to eliminate common problems.
2. Ensure the Circuit Breaker is not tripped (see Troubleshooting section).
If you still have problems or questions, please contact APC via the internet or at
the phone numbers listed in the Contact Information section.
3. Before contacting APC, please be sure to record the date purchased, model and
serial number (on bottom of unit).
4. Be prepared to troubleshoot the problem over the telephone with a Technical
Support Representative. If this is not successful, the representative will issue a
Return Material Authorization Number (RMA#) and a shipping address.
Pack the unit in its original packaging. If the original packaging is not available,
ask APC Technical Support about obtaining a new set. Pack the unit properly to
avoid damage in transit. Never use foam beads for packaging. Damage
sustained in transit is not covered under the warranty (insuring the package for
full value is recommended).
8. Write the RMA# on the outside of the package.
9. Return the unit by insured carrier to the address given to you by APC.
APC China (Phone) 8610-85299888
Website http://www.apcc.com/ch
Online Technical Support http://support.apcc.com/ch
American Power Conversion 132 Fairgrounds Road
West Kingston, RI USA 02892
Safety
This section contains important instructions that should be followed during installation
and maintenance of the Back-UPS. It is intended for APC customers who setup, install,
relocate, or maintain APC equipment.
This equipment is intended for installation in a temperature-controlled indoor area (see
Specifications for exact temperature range), free of conductive contaminants.
WARNING! Battery Safety
This unit contains no user-serviceable parts. This equipment contains
potentially hazardous voltages. Do not attempt to disassemble the unit.
Repairs are performed only by factory trained service personnel.
Do not dispose of batteries in a fire. The batteries may explode.
Do not open or mutilate batteries. They contain an electrolyte which is
toxic and harmful to the skin and eyes.
Batteries must be recycled. Deliver the entire Back-
UPS to an appropriate recycling facility, or ship it to APC
in the original packaging.
!