6.3 Computer Interface Port (600 VA only)
The computer interface port is diagramed below for your reference. Those with technical
abilities wishing to use this port in a special application should be aware of the following
limitations and capabilities of the interface.
6.4.1 Outputs at pins 3, 5 and 6 are actually open collector outputs which must be pulled
up to a common referenced supply no greater than +40 Vdc. The transistors are capable
of a maximum non-inductive load of 25 mAdc. Use only Pin 4 as the common.
6.4.2 The output at Pin 2 will generate a LO to HI RS-232 level upon transfer of the output
load to power derived from the UPS’s battery. The pin is normally at a LO RS-232 level.
6.4.3 The UPS will shut down when a HI RS-232 level, sustained for 0.5 s, is applied to Pin
1. The UPS responds to this signal, following a delay, only during utility failures (load is
operating from the UPS’s internal power source).