American Power Conversion PD80KL6FK1-M Power Supply User Manual


 
System Operation
80kW InfraStruXure PDU—Operation and Configuration 35
4. Close (turn ON) the UPS System Enable switch.
The UPS will show a Forced Bypass message on
the display interface, and the Fault LED will be
red.
5. Command the UPS to apply power to the load:
a. Press the
E
SC
key at the top-level status screen to
open the top-level menu and have access to eight
submenus.
b. Select Control, and press the
E
NTER
key.
Top-Level Menu
c. Select Turn Load On from the Control menu, and
press the
E
NTER
key.
Control Menu
d. On the next screen: select Yes, UPS Load ON, and
press the
E
NTER
key.
Confirmation Screen
The Load On LED illuminates and the interface displays the following two screens:
6. Command the UPS into static bypass operation through the UPS display interface:
a. Press the
E
SC
key at the top-level status screen to
open the top-level menu.
Top-Level Menu
b. Select Control on the top-level menu, and press the
E
NTER
key.
Control
Status
Setup
Accessories
Logging
Display
Diags
Help
UPS Into Bypass
Do Self Test
Simulate Power Fail
Graceful Reboot
Graceful Turn Off
Start Runtime Cal
Turn Load On
Confirm
Yes, UPS Load ON
No, Abort
UPS has been
commanded to turn
load power on...
UPS load is on
Press any key...
Control
Status
Setup
Accessories
Logging
Display
Diags
Help