American Power Conversion SURT15000 Power Supply User Manual


 
Smart-UPS RT 15000/20000 VA 230 Vac UXI/UXICH Tower User Manual 23
General
Status
# of batteries increased. At least one battery pair has been
added to the system.
No corrective action is necessary.
# of batteries decreased. At least one battery pair has been
removed from the system.
# External Battery Packs
increased.
At least one external battery pack has
been connected to the UPS.
# External Battery Packs
decreased.
At least one external battery pack has
been disconnected from the UPS.
Module
Failure
Bad Battery Pair. A battery pair has failed and requires
replacement.
Refer to battery pair installation in
the external battery pack user
manual.
Threshold
Alarm
Load Power Is Above
Alarm Limit.
The load has exceeded the user-
specified load alarm threshold.
Option 1) Use the display interface to
raise the alarm threshold.
Option 2) Reduce the load
Load Is No Longer Above
Alarm Threshold.
The load exceeded the alarm
threshold. The situation has been
corrected. Either because the load
decreased or the threshold was
increased.
No corrective action is necessary.
Min Runtime Restored. The system runtime dropped below
the configured minimum and has been
restored:
1) Additional battery modules were
installed.
2) The existing battery modules were
recharged.
3) The load was reduced.
4) The user- specified threshold was
decreased.
Condition
PowerView Display
Message
Reason for Message Corrective Action