5
About Your Step-Down Transformer
Table 1: System Configurations and Model Numbers
* Power cord connected units have an available power of 4500 VA with a L6-30 plug.
** Units with an available power of 5000 VA must be hardwired due to input current.
*** Ensure that the pin number for T-slot receptacles is correct.
Figure 1: Step-Down Transformer
This Step-Down Transformer is designed for use with a
UPS that provides a higher output voltage (200 or 208
VAC).
It converts the output to a lower voltage (100 or 120
VAC); a common voltage level used by many computers
and accessories.
The Step-Down Transformer may also be used as a
stand-alone device.
Complete
System–
End Item
SKU
Available
Power VA
Nominal
Input
Voltage
VAC
Nominal
Output
Voltage VAC
Frequency
Hz
Power
Distribution
AP9621,
SYTF2,
SURT005
4500*
5000**
208 120 60
Input: 3-foot cord with L6-
30P or hardwired.
*** Output: (2) 15-amp
circuits with (4) 5-20R
T-slots and (2) 15-amp
circuits with (2) 5-20R
T-slots, or hardwired.
North
America
and
208V
(Ø- Ø -G)
SYTF3,
SUTF3
4500 208 120 60
Input: 2-foot cord
with L6-30P.
*** Output: (4) 20-amp
circuits with (4) L5-20R.
SYTF2J,
SURT006
3500 200 100 50 or 60
Input: 3-foot cord with
L6-30P.
***Output: (2) 15-amp
circuits with (4) 5-20R
T-slots and (2) 15-amp
circuits with (2) 5-20R
T-slots.
Japan
and
200 V
(Ø- Ø -G)
SYTF3J 3500 200 100 50 or 60
Input: 2-foot cord
with L6-30P.
***Output: (4) 20-amp
circuits with (4) L5-20R.