American Power Conversion UXI/UXICH Power Supply User Manual


 
2
A
TTACH THE BEZEL TO THE UPS
H
ARDWIRING INSTRUCTIONS 5000 VA MODELS ONLY:
Wiring must be performed by a qualified electrician.
Adhere to all national and local electrical codes.
Install a high magnetic 30/32 A utility circuit breaker
Use #10 AWG gauge (5 mm
2
) wire.
1. Switch the utility circuit breaker OFF.
2. Remove the input access panel.
3. Remove circular knockout.
4. Run #10 AWG gauge (5 mm
2
) wire through the access panel, and connect the wires to the
terminal block (Green: Ground, Brown: Hot, Blue: Neutral). Use an appropriate strain relief (not
included).
5. Replace the access panel.