APC 6000 VA Power Supply User Manual


 
CSI SECTION 16611 STATIC UNINTERRUPTIBLE SYSTEM
3.2 SOFTWARE AND CONNECTIVITY
A. Network Adaptor: APC SmartSlot Network Management Card shall allow one or more
network management systems (NMS) to monitor and manage the UPS in TCP/IP
network environments.
B. Unattended Shutdown
1. The UPS, in conjunction with a network interface card, shall be capable of
gracefully shutting down one or more operating systems during when the UPS is
on battery mode.
2. The UPS is also capable of using an RS232 port to communicate to the host
computer by means of serial communications so as to gracefully shut down one
or more operating systems during an on battery situation. The PowerChute
Business Edition software is available from APC and must be purchased
separately.
3.3 REMOTE UPS MONITORING, CONFIGURATION AND CONTROL
A. The following three methods of remote UPS control, configuration and monitoring are
available:
1. Web Monitoring: Remote monitoring, configuration and control is available via a
web browser such as Internet Explorer provided the UPS is equipped with
2. Monitoring, configuration and control via PowerView Remote Display, four line
multilingual intelligent alphanumeric LCD (up to 15 feet/5meters away);
3. Dry contact monitoring and control provided the UPS is equipped with APC
SmartSlot Relay I/O Card.
3.4 SOFTWARE COMPATIBILITY
A. A: Included with the UPS is PowerChute Business Edition Basic (5-node) software.
The software supports graceful shutdown and remote monitoring for the following
systems:
1. Windows 2003
2. Windows NT 4.0 with Service Pack 6
3. Windows 2000 with Service Pack 3
4. Windows XP
5. Red Hat Linux v.7.3, 8.0 and 9.0
6. SuSE v.8.0 and 8.1
CSI SECTION 16611 STATIC UNINTERRUPTIBLE SYSTEM