APC 6000 VA Power Supply User Manual


 
CSI SECTION 16611 STATIC UNINTERRUPTIBLE SYSTEM
1. Ensure proper system start-up.
2. Verify proper firmware control functions.
3. Verify proper firmware bypass operation.
4. Verify proper bypass switch operation (where applicable).
5. Verify proper inverter operation and regulation circuits.
6. Simulate utility power failure.
7. Verify proper charger operation.
8. Document, sign, and date all test results.
E. On-Site Operational Training: During the factory assisted start-up, operational training
for site personnel shall include key pad operation, LED indicators, start-up and
shutdown procedures, maintenance bypass and AC disconnect operation, and alarm
information.
4.2 MANUFACTURER FIELD SERVICE
A. Worldwide service: The UPS manufacturer has a worldwide service organization
available, consisting of factory trained field service personnel to perform start-up,
preventative maintenance, and service of the UPS system and power equipment. The
service organization offers 24 hours a day, 7 days a week, 365 days a year service
support.
B. Replacement parts: Parts are available through the worldwide service organization 24
hours a day, 7 days a week, 365 days a year. The worldwide service organization is
capable of shipping parts within 4 working hours or on the next available flight, so that
the parts may be shipped to the customer site within 24 hours.
4.3 MAINTENANCE CONTRACTS
A. A complete offering of preventative and full service maintenance contracts for the UPS
system and the battery system are available from APC. All contract work is performed
by APC factory trained service personnel.
4.4 TRAINING
A. UPS service training workshop: A UPS service training workshop is available from
APC. The service training workshop includes a combination of lecture and practical
instruction with hands-on laboratory sessions. The service training workshop includes
instruction about safety procedures, UPS operational theory, sub-assembly
CSI SECTION 16611 STATIC UNINTERRUPTIBLE SYSTEM