CSI SECTION 16611 STATIC UNINTERRUPTIBLE SYSTEM
2.1 MECHANICAL DESIGN
A. The UPS is contained in a rugged steel cabinet with two plastic front bezels;
B. The UPS dimensions are 13 x 43 x 66cm (5.1 x 17 x 26 in.);
C. The UPS cabinet is capable of conversion between Tower and Rack-Mount
configurations;
2.2 SYSTEM CHARACTERISTICS
A. System Capacity:
1. The system is rated to be capable of supporting:
a. 3000VA or 2100W whichever limit is reached first (for the 3000VA
model).
b. 5000VA or 3500W whichever limit is reached first (for the 5000VA
model).
c. 6000VA or 4200W whichever limit is reached first (for the 6000VA
model).
B. The UPS efficiency is at least 91% for the 3000VA model and at least 92% for the
5000VA and 6000VA, without degradation of output regulation as specified.
C. Input:
1. AC input nominal voltage: 220/230/240VAC, single phase, 3 wire (L + N + G),
hardwired (5000VA and 6000VA models) or connected via IEC-320 C20
connector (3000VA models).
2. AC input voltage window:
a. 160 – 280VAC (L-N) at full load, while providing nominal charging to the
battery system;
b. 100 – 280VAC (L-N) at 50% load, while providing nominal charging to
the battery system;
3. Input frequency range: 45-65Hz;
4. Input Power Factor: Minimum 0.95 lagging at 100% load at 230VAC;
5. Input Current Distortion: Maximum 6% at 100% load at 230VAC;
6. Crest factor: 3:1.
D. UPS Output:
1. AC Output Nominal Output: 200VAC, 208VAC, 220VAC, 230VAC or
240VAC, user-selectable, Single Phase, 3 wire (Phase + N + G);
2. Output connectors: 8 IEC 320 C13 and 2 IEC 320 C19;
CSI SECTION 16611 STATIC UNINTERRUPTIBLE SYSTEM