Page 39
9.9 Typical recharge time and run time versus load
9.9.2 2000VA models
Number Of
1 2 3 4 5 6 7 8 9 10
10 plus
adder
* recharge to 90% of capacity
Battery Packs subsequent discharge into
Recharge
Time*
2.2 hr 4.5 hr 6.8 hr 9.2 hr 11.8 hr 14.2 hr 16.5 hr 19.2 hr 21.9 hr 24.0 hr + 2.4 hr
50% of rated load
Computer Load Typical computer load
(Volt-Amps) (p.f. typically 0.6 to 0.7)
200 VA
2.9 hr 6.2 hr 9.8 hr 14.4 hr 19.2 hr 24.1 hr 28.8 hr 32.9 hr 37.0 hr 41.1 hr + 4.1 hr
IBM PS/2 55sx w/ VGA monitor
250 VA
2.5 hr 5.3 hr 8.4 hr 11.8 hr 16.1 hr 20.3 hr 24.6 hr 28.6 hr 32.2 hr 35.8 hr + 3.6 hr
Compaq 386/25e w/ VGA monitor
300 VA
2.2 hr 4.7 hr 7.3 hr 10.1 hr 13.6 hr 17.4 hr 21.2 hr 24.9 hr 28.5 hr 31.7 hr + 3.2 hr
Compaq 386/33 w/ VGA monitor
350 VA 1.9 hr 4.2 hr 6.5 hr 8.9 hr 11.7 hr 15.0 hr 18.4 hr 21.8 hr 25.1 hr 28.3 hr + 3.2 hr
IBM PS/2 95 file server
400 VA 1.7 hr 3.7 hr 5.8 hr 8.0 hr 10.2 hr 13.1 hr 16.1 hr 19.2 hr 22.2 hr 25.3 hr + 3.1 hr
Compaq 386/33 w/ 19" monitor
500 VA
1.4 hr 3.1 hr 4.8 hr 6.5 hr 8.4 hr 10.3 hr 12.6 hr 15.2 hr 17.7 hr 20.3 hr + 2.6 hr
Compaq Systempro server
600 VA
1.1 hr 2.6 hr 4.0 hr 5.5 hr 7.1 hr 8.7 hr 10.2 hr 12.3 hr 14.5 hr 16.6 hr + 2.1 hr
(2) Compaq 386/33 w/ monitors
700 VA
0.9 hr 2.2 hr 3.5 hr 4.7 hr 6.0 hr 7.4 hr 8.8 hr 10.2 hr 11.9 hr 13.8 hr + 1.9 hr
(2) IBM PS/2 95 file servers
800 VA
0.8 hr 1.9 hr 3.0 hr 4.2 hr 5.3 hr 6.5 hr 7.7 hr 8.9 hr 10.1 hr 11.6 hr + 1.5 hr
IBM AS/400 D20 minicomputer
900 VA 0.7 hr 1.7 hr 2.7 hr 3.7 hr 4.7 hr 5.7 hr 6.8 hr 7.9 hr 9.0 hr 10.1 hr + 1.1 hr
DEC MicroVax
1000 VA
0.6 hr 1.5 hr 2.4 hr 3.3 hr 4.2 hr 5.1 hr 6.0 hr 7.0 hr 8.0 hr 9.0 hr + 1.0 hr
(2) Compaq Systempro servers
1200 VA
0.5 hr 1.2 hr 1.9 hr 2.7 hr 3.4 hr 4.2 hr 4.9 hr 5.7 hr 6.5 hr 7.3 hr + 0.8 hr
(4) Compaq 386/33 w/ VGA mon.
1600 VA
0.3 hr 0.8 hr 1.3 hr 1.9 hr 2.4 hr 3.0 hr 3.5 hr 4.1 hr 4.7 hr 5.2 hr + 0.6 hr
(8) IBM PS/2 55sx w/ VGA mon.
2000 VA
0.2 hr 0.6 hr 1.0 hr 1.4 hr 1.8 hr 2.3 hr 2.7 hr 3.1 hr 3.6 hr 4.0 hr + 0.5 hr
(4) Compaq Systempro servers
Note: Run times are typical at 25°C (77°F). Add the values given in the "10 plus adder" column to the values given in
the "10" column for each Battery pack installed above a total of 10. Example: When 13 Battery packs are installed, the
recharge time is typically less than 24 + 2.4 + 2.4 + 2.4 = 31.2 hrs. The run time for this system at full load is typically
greater than 4.0 + 0.5 + 0.5 + 0.5 = 5.5 hrs.