3402230800/AC - 5
The Network Management Card & Modbus/Jbus (66123) can be hot-plugged in MGE
TM
Galaxy
TM
7000
equipped with a Minislot. It is not necessary to shutdown the UPS, disconnect the load or restart the UPS.
◗ Note the MAC address of the card before inserting it.
◗ Insert and secure the card with the screws.
◗ Connect the ETHERNET cable.
◗ Check the ETHERNET port indications.
◗ Wait until the UPS Data LED flashes regularly (approx. two minutes), indicating that card start-up has
terminated correctly.
Note. Connection detection continues until the card has been connected to the network. Once connection is
made, card start-up continues.
Once the card has started, proceed as indicated below.
◗ Connect the serial cable to card’s service port and PC’s COM port
◗ Use a terminal emulator such as HyperTerminal
TM
with these settings
"Echo typed characters locally" option: disabled
◗ Type MGEUPS (or mgeups).
The main configuration menu is displayed:
IP SETTINGS
Bits per second Data bits Stop bits Parity Flow control
9600 8 1 none none
APC by Schneider Electric
Network Management Card & Modbus/Jbus
Release : AB.build_5_0_7
1 : Reset
2 : Network configuration
3 : Set Login Password to Default
4 : Return to Default Configuration
5 : Jbus configuration
6 : Sensor configuration
0 : Exit