APC 990 Switch User Manual


 
Operation: Operation Procedures
Symmetra MW with External Bypass Static Switch Operation Manual - 990-1377D-001 11
Press the Shutdown button. Press inside the
password field and type in the user password using
the keyboard on the screen. Complete with Enter.
Follow the procedure on the screen which is specific
to your system.
How to transfer from normal to static bypass operation
Press the Operation button on the UPS Summary
screen.
Press the Online -> Static Bypass button. Press
inside the password field and type in the user
password using the keyboard on the screen.
Complete with Enter.