6
NOTE: SETTINGS ARE ADJUSTED THROUGH POWERCHUTE SOFTWARE
OR OPTIONAL SMART SLOT ACCESSORY CARDS.
FUNCTION
F
ACTORY
D
EFAULT
U
SER SELECTABLE
CHOICES
DESCRIPTION
High Transfer
Point
100V model:
108 Vac
120V model:
127 Vac
230V model:
253 Vac
100V model:
108, 110, 112, 114
Vac
120V model:
127, 130, 133, 136
Vac
230V model:
253, 257, 261, 265
Vac
Set the high transfer point higher to
avoid unnecessary battery usage when
the utility voltage is usually high and
the connected equipment is specified
to operate with input voltages this
high.
Low Transfer Point 100V model:
92 Vac
120V model:
106 Vac
230V model:
208 Vac
100V model:
86, 88, 90, 92 Vac
120V model:
97, 100, 103, 106
Vac
230V model:
196, 200, 204, 208
Vac
Set the low transfer point lower when
the utility voltage is usually low and
the connected equipment is specified
to operate with input voltages this low.
Output Voltage
(230V model only)
230 Vac 220, 230, 240 Vac Select the output voltage.