APC AP88XX Surge Protector User Manual


 
32Metered Rack PDU User Guide
bkOverLoad
Access: Administrator, Device User
Description: Set or view the bank overload threshold current in amps. You can specify all banks, a
single bank, a range, or a comma-separated list of single banks and/or ranges.
Example 1: To set the bank overload threshold for all banks to 13A, type:
apc> bkOverLoad all 13
E000: Success
Example 2: To view the bank overload threshold setting for banks 1 through 3, type:
apc> bkOverLoad 1-3
E000: Success
1: 13 A
2: 13 A
3: 13 A
bkReading
Access: Administrator, Device User
Description: View the current reading (measurement) in amps for a bank. You can specify all banks, a
single bank, a range, or a comma-separated list of single banks and/or ranges.
Example 1: To view the current reading for bank 3, type:
apc> bkReading 3
E000: Success
3: 4.2 A
Example 2: To view the current reading for all banks, type:
apc> bkReading all
E000: Success
1: 6.3 A
2: 5.1 A
3: 4.2 A
devLowLoad
Access: Administrator, Device User
Description: Set or view the low-load threshold in kilowatts for the device.
Example 1: To view the low-load threshold, type:
apc> devLowLoad
E000: Success
0.5 kW
Example 2: To set the low-load threshold to 1 kW, type:
apc> devLowLoad 1.0
E000: Success
Example 3: To set the low-load threshold to 1.5 kW on guest Rack PDU 3, type:
apc> devLowLoad 3:1.5
E000: Success