APC AP9606 Network Card User Manual


 
8
Expansion/Triple Chassis Installation
continued
Step 3: Install
the Web/SNMP
Management
Card
Caution:
If the UPS uses more than one APC management
peripheral, see the supplied
Installation of Multiple
SmartSlot Cards
sheet. You must install the APC
peripherals in the correct order, otherwise the
peripherals may fail to operate properly.
1. If PowerChute
plus
is installed, stop the PowerChute
plus
service and disconnect its cable from the UPS serial port.
2. Use the screws that hold the expansion slot cover in place
to secure the Management Card in the chassis slot.
3. Connect a network interface cable to the Management
Card’s 10Base-T network connector.
4. If you are using the optional AC Adapter (AP9505), do
the following:
a. Connect the adapter to the chassis.
b. Connect the adapter to an independent AC input so that
the Management Card can continue to operate if the
UPS is turned off or fails.
5. If neccessary, reconnect the PowerChute
plus
cable.
6. If neccessary, restart the PowerChute
plus
service.
7. See “Quick Configuration” on page 9.
Figure 2: Installing a Management Card in a SmartSlot Expansion
Chassis (AP9600)