APC AP9631 Network Card User Manual


 
23UPS Network Management Card 2 User’s Guide
ups
Access: Administrator, Device User
Description: Control the UPS and view status information.
Example 1: To initiate a runtime calibration, type:
ups -r start
Option Arguments Description
-c off | graceoff | on |
reboot | gracereboot |
sleep | gracesleep
Configure UPS actions. See “Actions (for a single UPS and
Synchronized Control Groups)” on page 33 for detailed information.
-r start | stop Initiate or end a runtime calibration. A calibration recalculates remaining
runtime and requires the following:
• Because a calibration temporarily depletes the UPS batteries, you can
perform a calibration only if battery capacity is at 100%.
• For some UPSs, the load must be at least 7% for a calibration to be
performed.
-s start Initiate a UPS self-test.
-b enter | exit Control the use of bypass mode. This command is model-specific and
may not apply to your UPS. See “Actions (for a single UPS and
Synchronized Control Groups)” on page 33 for detailed information.
-o# off | delayoff | on |
delay on | reboot |
delayreboot
Control three outlet groups at a Smart-UPS XLM. For information about
outlet groups, see “Outlet Groups” on page 38.
When the state of the outlet group is on, the option accepts three
arguments:
off—Turn off the group immediately.
delayoff—Turn off the group after the number of seconds configured
as Power Off Delay.
reboot—Turn off the group immediately, then turn it on after the
number of seconds configured as Reboot Duration and Power On
Delay.
delayreboot—Turn the outlet group off after the number of seconds
configured as Power Off Delay, then turn it on after the number of
seconds configured as Reboot Duration and Power On Delay.
When the state of the outlet group is off, the option accepts two
arguments:
on—Turn on the group immediately.
delayon—Turn on the group after the number of seconds configured
as Power On Delay.
The Power On Delay, Power Off Delay, and Reboot Duration must be
configured at the Web interface. See “The settings option (including
automatic load-shedding)” on page 40 for more information.
-os# View the status (on, off, or rebooting) of all of the outlet groups. To view
the status of a specific outlet group, specify its number. For example,
type
ups -os1 to view the status of outlet group 1.
-st View the status of the UPS.