16 User Guide Silcon DP300E Series 480V 120-160kVA
7OA0003 US rev. 03
4.0 Programming Parameters
4.1 General
Some operating parameters can be programmed directly from the keyboard. Unless
you are quite sure of the consequence of changing the following parameters, please
contact your local APC dealer for assistance.
Parameters are programmed as shown in the example 4.2.3.
4.2 Parameters
4.2.1
Parameter Setting* Comments
Bypass YES, NO “YES” will switch the system into
bypass mode
Language GB, D, F, I, Language of text in display
DK, S, SF,
NL, PL, CZ,
E, P, SK, H
Autostart YES, NO Automatic restart of UPS upon utility return.
Ensures quick battery recharge.
Remote shutdown YES, NO Shutdown of UPS by remote signal
active
Remote shutdown HIGH, LOW Nature of remote shutdown signal polarity
polarity
Remote shutdown time 0, 1, 2, 3, 4 Time delay on remote shutdown of UPS
5, 6, 7, 8, 9
10 min.
Battery capacity test - Initiates check of back-up time. The
measured time is from start until it reaches
low DC warning level (See section 8.4)
Battery monitor test** - Initiates check of battery condition by
25% discharging.
Automatic battery test** NO, 3, 6 Activates the battery monitor test in cyclic
intervals (Unit - months)
Battery monitor reset** - Pressing the
and key after
selecting this parameter resets any battery
alarms.
Boost charge YES, NO “YES” results in boost charge (10 hours)
Autoboost charge YES, NO “YES” results in boost charge after every
battery operation (10 hours)
Enter new date YYMMDD Local date can be entered
Enter new time HHMMSS Local time can be entered (24 hour clock)
* Text in bold letters are the standard setting
** Only for systems with battery monitor active
Programming Parameters
NOTE:
The system must not run in
bypass mode for extended
periods of time as the batteries
will not be charged.