5
4: USER CONFIGURABLE ITEMS
NOTE: SETTINGS ARE ADJUSTED THROUGH POWERCHUTE BUSINESS EDITION SOFTWARE
FUNCTION
FACTORY
DEFAULT
USER SELECTABLE
CHOICES
DESCRIPTION
Automatic
Self-Test
Every 14 days
(336 hours)
Every 7 days
(168 hours),
Every 14 days
(336 hours),
On Startup Only,
No Self-Test
Set the interval at which the UPS will
execute a self-test.
UPS ID UPS_IDEN Up to eight charac-
ters (alphanumeric)
Uniquely identify the UPS, (i.e. server
name or location) for network man-
agement purposes.
Date of Last
Battery
Replacement
Manufacture Date mm/dd/yy Reset this date when you replace the
battery module.
Minimum Capacity
Before Return from
Shutdown
0 percent 0, 15, 50, 90 percent Specify the percentage to which batter-
ies will be charged following a low-
battery shutdown before powering
connected equipment.
Voltage Sensitivity
The UPS detects
and reacts to line
voltage distortions
by transferring to
battery operation to
protect connected
equipment.
High High sensitivity,
Medium sensitivity,
Low sensitivity
Note: In situations of poor power qual-
ity, the UPS may frequently transfer to
battery operation. If the connected
equipment can operate normally under
such conditions, reduce the sensitivity
setting to conserve battery capacity
and service life.
Alarm Delay After
Line Fail
5 seconds 5 second delay,
30 second delay,
At low battery
condition,
No alarm
Set the delay to avoid alarms for minor
power glitches.
Shutdown Delay 60 seconds 60, 180, 300, 600
seconds
Set the interval between the time when
the UPS receives a shutdown com-
mand and the actual shutdown.