APC SURTA3000XL Power Supply User Manual


 
10 Smart-UPS RT 2400/3000 VA Tower/Rack-Mount UPS User Manual
Configuration Settings
Configuration Settings
Settings are adjusted through PowerChute software, optional SmartSlot accessory cards, or in terminal
mode.
Function
Factory
Default
User Selectable
Choices
Description
Automatic
Self-Test
Every 14 days
(336 hours)
Every 7 days
(168 hours)
Every 14 days
(336 hours)
On start up only
No self-test
Set the interval at which the UPS will execute a
self-test.
UPS ID UPS_IDEN Up to eight characters
(alphanumeric)
Uniquely identify the UPS, (i.e. server name or
location) for network management purposes.
Date of Last
Battery
Replacement
Manufacture
Date
mm/dd/yy Reset this date when you replace the battery
module.
Minimum
Capacity Before
Return from
Shutdown
0 percent 0%
•15%
•30%
•45%
•60%
•75%
•90%
Specify the percentage to which batteries will be
charged following a low battery shutdown before
powering connected equipment.
Alarm Delay Enable Enable
•Mute
Disable Mute ongoing alarms or disable all alarms
permanently.
Shutdown Delay 90 seconds 0 s
•90 s
•180 s
•270 s
•360 s
•450 s
•540 s
•630 s
Set the interval between the time when the UPS
receives a shutdown command and actual
shutdown.
Low Battery
Warni ng
2 minutes 2 m
•5 m
•8 m
•11 m
•14 m
•17 m
•20 m
•23 m
PowerChute software interface provides
automatic, unattended shutdown when
approximately two minutes of battery operated
run time remains.
The low-battery warning beeps are continuous
when two minutes of run time remain.
Change the low battery warning interval setting to
the time that the operating system or system
software requires to safely shut down.
Synchronized
Turn-on Delay
0 seconds 0 s
•60 s
•120 s
•180 s
•240 s
•300 s
•360 s
•420 s
Specify the time the UPS will wait after the return
of utility power before start up (to avoid branch
circuit overload).