Turn the UPS Load Off
1. Select UPS and press ENTER.
→ UPS Alarms
Power Dist Log
Switch Gear Admin
Environment Help
2. Select UPS Power Control and press ENTER.
→ UPS Power Control
UPS Status
UPS Tests & Diags
UPS Configuration
3. Select Turn UPS Off and press ENTER.
→ Turn UPS Off
Reboot UPS
UPS Into Bypass
UPS To Sleep
4. Select No, Don’t Notify and press ENTER.
Note: This action will cut all power
to the load without shutting it off
rst. If you want to shut down the
servers rst, then choose Yes, Notify
Servers.Note that this function
is only available for servers with
PowerChute.
Notify PowerChute?
Cancel
Yes, Notify Servers
→ No, Don't Notify
5. Conrm YES, Turn UPS Off and press
ENTER.
Turn UPS Off Without
Server Notification?
>NO, ABORT
→ YES, Turn UPS Off
6. Wait for the UPS to turn off.
Turning UPS off,
please wait...
12
Symmetra™ PX48, 96, and 160 kW 400 V 100 kW 208 V Operation
990–3015E-001