Atlantis Land A03-PS651 _MX01 Power Supply User Manual


 
OnePower Line Interactive UPS
A03-PS651 Pag. 43
Net
Weight(with
Battery):
6.0 Kg
Temperature 5°-40° C ENVIRONMENTS
Humidity 0-90% (non-condensing)
CERTIFICATION CE
Backup TIME
A03-PS651
PentiumIV 3.0 Ghz + LCD 17”
PentiumIV 3.2 Ghz + LCD 17”
PentiumIV 3.4 Ghz + LCD 19”
Power Rating(VA) 200 300 400 500 550 600
Power Rating(W) 120 180 240 300 330 375
Backup Time(minute)
16 9 5 4 3 2
AVR
A03-PS651
Vin(V)
AVR Vout(V) Note
Vin<165 N/A Inv (220+/- 10%)
the UPS returns to AC
output mode when AC
input increase to 177V
165<Vin<205 Increase (15%) 190<Vout<235
206<Vin<249 N/A 206<Vout<249
250<Vin<280 Decrease (11%)
223<Vout<250
Vin>280
N/A
Inv (220+/- 10%)
The UPS returns to AC
output mode when AC
input drops to 270V