Black Box LES114BA Server User Manual


 
# config -s config.cascade.slaves.slave1.address=192.168.0.153
# config -s "config.cascade.slaves.slave1.description=CM in office 42"
# config -s config.cascade.slaves.slave1.label=les1116-5
# config -s config.cascade.slaves.slave1.ports=16
The total number of slaves must also be incremented. If this is the first slave you’re adding, type:
# config -s config.cascade.slaves.total=1
Increment this value when adding more slaves.
NOTE: If a slave is added using the CLI, then the master SSH public key will need to be manually copied
to every slave device before cascaded ports will work (refer Chapter 4).
The following command will synchronize the live system with the new configuration:
# config -r cascade
14.9 UPS Connections
Managed UPSes
Before adding a managed UPS, make sure that at least 1 port has been configured to run in 'device
mode', and that the device is set to 'ups'.
To add a managed UPS with the following values:
Connected via Port 1
UPS name My UPS
Description UPS in room 5
Username to connect to UPS User2
Password to connect to UPS secret
shutdown order 2 (0 shuts down first)
Driver genericups
Driver option - option option
Driver option - argument argument
Logging Enabled
Log interval 2 minutes
Run script when power is critical Enabled
# config -s config.ups.monitors.monitor1.port=/dev/port01
If the port number is higher than 9, eg port 13, enter:
# config -s config.ups.monitors.monitor1.port=/dev/port13
# config -s "config.ups.monitors.monitor1.name=My UPS"
# config -s "config.ups.monitors.monitor1.description=UPS in room 5"
# config -s config.ups.monitors.monitor1.username=User2
# config -s config.ups.monitors.monitor1.password=secret
# config -s config.ups.monitors.monitor1.sdorder=2
# config -s config.ups.monitors.monitor1.driver=genericups
# config -s config.ups.monitors.monitor1.options.option1.opt=option
# config -s config.ups.monitors.monitor1.options.option1.arg=argument
# config -s config.ups.monitors.monitor1.options.total=1
# config -s config.ups.monitors.monitor1.log.enabled=on
# config -s config.ups.monitors.monitor1.log.interval=2
# config -s config.ups.monitors.monitor1.script.enabled=on
_____________________________________________________________________