Remote Module LED Status Indicators
Symphony II System does not communicate or manage
appliances/loads when utility power is present.
NOTICE When looking at LED’s, make sure you look
straight on and not at an angle.
Low Voltage (Single and Dual) Models
LED is for signal communication status (C).
Utility power present:
• NormalState
- Orange LED - No communication and appliances/
loads cannot be managed by Symphony II System
• ProblemState(seeTroubleshooting)
- No LED - No power to low voltage control board;
verify correct wiring
- Green LED - Broken LED; replace low
voltage module
- Red LED - Fault in system; verify current
transformer connections, verify terminations on
orange and yellow communication wires
Generator power present:
• NormalState
- Green LED - Signal communication detected and
appliances/loads can be managed after
5 minute delay
• ProblemState(seeTroubleshooting)
- No LED - No power to low voltage control board;
verify correct wiring
- Orange LED - Signal communication not detected;
verify correct wiring
- Red LED - Fault in system; verify current
transformer connections, verify terminations on
orange and yellow communication wires
A
C
DE
B
A - Low Voltage Control Wiring Terminal Contacts
B - Priority Selector
C - Communication LED
D - Neutral Connection
E - Power/Line Connection