Bryant 583A Switch User Manual


 
PERFORMANCE DATA (cont)
DRY COIL AIR DELIVERY* HORIZONTAL AND DOWNFLOW DISCHARGE UNIT SIZES 024-060
(Deduct 10% for 208 Volts)
230 AND 460 VOLT
Unit
583A
Motor Speed
External Static Pressure (in. wg)
0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
024
Low
Watts 281282281278276——————
Cfm 899828757691619——————
Med
Watts 375 370 363 357 352
Cfm 969 897 824 744 649
High
Watts —————468457444431423
Cfm —————994913826730620
030
Low
Watts 246244243241———————
Cfm 982860808736———————
Med
Watts 343339336332328322317————
Cfm 1233 1170 1109 1038 953 855 754 ————
High
Watts ————441432421410400——
Cfm ————1202 1111 1021 929 826
036
Low
Watts 470 458 445 430 415 399 384
Cfm 1463 1406 1344 1273 1188 1091 983
Med
Watts 514 501 487 471 455 438 422
Cfm 1497 1428 1348 1255 1152 1042 929
High
Watt 646 636 626 614 602 589
Cfm 1491 1412 1325 1128 1120 1003
042
Low
Watts 643 625 614 605 593 574 549 518 485 454
Cfm 1626 1614 1579 1532 1478 1421 1361 1295 1218 1120
Med
Watts ————726695661625591561540
Cfm ————1731 1672 1610 1541 1456 1345 1193
High
Watts ———————790766742713
Cfm ———————1699 1602 1494 1367
048
Low
Watts 614 588 577 572 566 556 539 517 491
Cfm 1591 1549 1581 1490 1460 1421 1372 1312 1242
Med
Watts 778 756 738 719 699 676 650 623 596 572 555
Cfm 1854 1837 1804 1759 1705 1643 1577 1508 1440 1375 1315
High
Watts ————896862829800775752728
Cfm ————1956 1879 1797 1709 1615 1514 1406
060
Low
Watts 903 898 873 842 814 792 777 764 743 701 618
Cfm 2249 2220 2149 2066 1988 1923 1871 1821 1751 1632 1424
Med
Watts 1002 978 960 941 914 880 839 798 764 750
Cfm 2465 2366 2272 2181 2091 2001 1909 1815 1718 1617
High
Watts 1080 1080 1066 1041 1008 972 938
Cfm 2390 2266 2208 2144 2041 1903 1772
*Air delivery values are without air filter and are for dry coil. (See Wet Coil Pressure Drop table.)
NOTE: Deduct field-supplied air filter pressure drop and wet coil pressure drop to obtain external static
pressure available for ducting.
15