Cisco Systems ONS 15600 OC48/STM 16 Laptop Docking Station User Manual


 
Corporate Headquarters:
Copyright © 2003-2007. Cisco Systems, Inc. All rights reserved.
Cisco Systems, Inc., 170 West Tasman Drive, San Jose, CA 95134-1706 USA
Installing the Cisco ONS 15600 OC48/STM16
LR/LH 16 Port 1550 Card
Note The terms "Unidirectional Path Switched Ring" and "UPSR" may appear in Cisco literature. These terms
do not refer to using Cisco ONS 15xxx products in a unidirectional path switched ring configuration.
Rather, these terms, as well as "Path Protected Mesh Network" and "PPMN," refer generally to Cisco's
path protection feature, which may be used in any topological network configuration. Cisco does not
recommend using its path protection feature in any particular topological network configuration.
Product Name: 15600-48L16-LR1550=
This document contains a description of OC48/STM16 LR/LH 16 Port 1550 card features, installation
procedures, removal instructions, and technical specifications. Use this document in conjunction with
the Cisco ONS 15600 Reference Manual, the Cisco ONS 15600 Procedure Guide, and the Cisco ONS
15600 Troubleshooting Guide when working with OC48/STM16 LR/LH 16 Port 1550 cards.
This document contains the following sections:
“OC48/STM16 LR/LH 16 Port 1550 Card” section on page 2
“OC48/STM16 LR/LH 16 Port 1550 Specifications” section on page 7
“Replace an OC-48 Card” section on page 8
“Obtaining Documentation” section on page 12
“Obtaining Technical Assistance” section on page 14
This document contains the following procedures:
“Replace an OC-48 Card” procedure on page 8
Note For information about circuits and card capacities, see the Cisco ONS 15600 Reference Manual.
Warning
Only trained and qualified personnel should be allowed to install, replace, or service this equipment.