Dell 5600W Power Supply User Manual


 
Dell UPS Site Preparation Guide, EMEA (230V) Revision 2, December 2012
Dell UPS Site Preparation Guide, EMEA.
Applies Dell Rackmount UPS Models, 3750W, 4200W, 5600W & 10kW
Note: This document is for guidance only. Actual installation instructions and safety cautions are included within the UPS User’s
Guide. Quick link to User’s Guides: http://dellups.com/support_download.asp > User Manuals and Publications.
Site Preparation Checklist
Installation site meets minimum environmental requirements.
Ensured all required accessories have been ordered with the UPS.
Electrical Preparation
Required electrical supply is available.
Scheduled an electrician to install the Dell UPS.
Provided a copy of this preparation guide to the electrician.
Made electrician aware of Hardwiring the UPS electrician’s checklist in the User’s Guide.
Site Preparation:
Physical Requirements for the Dell UPS
UPS Model
UPS Technology
Dimensions (mm, W x D x H)
Weight (installed, no battery)
3750W Rack
Online
4U, 438 x 790 x 171.5
65kg, 23kg
4200W Rack
Online
4U, 438 x 790 x 171.5
65kg, 23kg
5600W Rack
Line Interactive
4U, 438 x 790 x 171.5
72kg, 24kg
5600W Rack
Online
4U, 438 x 790 x 171.5
64kg, 24kg
10kW Rack
Online
5U, 438 x 823 x 214
110kg, 46kg
EBM* for 3750W/4200W
UPS
n/a
3U, 438 x 735 x 127
61kg, n/a
EBM* for all 5600W UPS
n/a
4U, 438 x 735 x 171.5
66kg, n/a
EBM* for 10kW
n/a
3U, 438 x 737 x 127
80kg, n/a
* EBM is an optional ‘external battery module’.
Environmental Requirements for the Dell UPS
Environmental Condition
Suitable Range
Temperature (Operation)
0 - 40C (32 - 104F)
Temperature (Storage, 24hr)
-15 - 60C (5 - 140F)
Temperature (Long-term Storage)
- 15 - 45C (5 - 113F)
Relative Humidity
0 - 95% (non-condensing)
Elevation (Operation)
0 - 3048m (0 - 10,000ft)
Elevation (Storage)
0 - 15,340m (0 - 50,000ft)
Heat Output for the Dell UPS
UPS Model
UPS Technology
Heat Loss, Watts / BTU (normal mode)
Heat Loss, Watts / BTU (battery mode)
3750W Rack
Online
188 / 640
375 / 1281